E5CB

Cost effective performance

The new E5CB represents our dual-display solution in the basic temperature controller segment. With eight models to choose from and all featuring the unique 2-PID control algorithm, this series provides you with the best control available. All models have an alarm relay and auto-tuning as standard.

  • Precise control using our unique 2-PID system
  • Easy to read from a distance via large 16.2 mm PV display
  • Low unit depth (only 60 mm)

Specifications & ordering info

Ordering information

Size

Power supply voltage

Input type

Alarm output

Control output

Order code

E5CB
48 × 48 mm

100 to 240 VAC

Thermocouple

1

Relay output

E5CB-R1TC

Platinum resistance thermometer

E5CB-R1P

Thermocouple

Voltage output
(for driving SSR)

E5CB-Q1TC

Platinum resistance thermometer

E5CB-Q1P

24 VAC/VDC

Thermocouple

Relay output

E5CB-R1TCD

Platinum resistance thermometer

E5CB-R1PD

Thermocouple

Voltage output
(for driving SSR)

E5CB-Q1TCD

Platinum resistance thermometer

E5CB-Q1PD

Accessories

Option

Order code

USB-Serial conversion cable

E58-CIFQ2

Software

Description

Features

ThermoMini

Freeware/Parameter copying and cloning tool
Parameter export (.csv), self-expressing

Specifications

Item

E5CB

Power supply voltage

100 to 240 VAC 50/60 Hz, 24 VAC 50/60 Hz, or 24 VDC

Operating voltage range

85% to 110% of rated supply voltage

Power consumption

Approx. 3.5 VA (100 to 240 VAC)
Approx. 3.5 VA (24 VAC)
Approx. 2.5 W (24 VDC)

Sensor input

Models with thermocouple inputs

Thermocouple: K, J, T, R, or S (JIS C 1602-1995, IEC60584-1)

Models with platinum resistance thermometer inputs

Platinum resistance thermometer: Pt100 (JIS C 1604-1997, IEC60751)

Control output

SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations,
minimum applicable load: 5 V, 10 mA

Output voltage: 12 VDC +25%/−15% (PNP), max. load current: 21 mA, with short-circuit protection circuit

Alarm output

SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations, minimum load: 5 V, 10 mA

Control method

ON/OFF control or 2-PID control (with auto-tuning)

Setting method

Digital setting using front panel keys

Indication method

7-segment digital display and individual indicators

Character height: 16.2 mm (PV)

Other functions

Temperature input shift, run/stop, protection functions, etc.

Ambient operating
temperature

−10 to 55°C (with no condensation or icing)/With a three-year guarantee: −10 to 50°C

Ambient operating humidity

25% to 85%

Storage temperature

−25 to 65°C (with no condensation or icing)

Size in mm (H × W × D)

48×48×65

Note: Other models (E5C_L/E5EW) with similar features but without USB communication are only available for “Emerging Countries”. Please ask you local Sales representative for further information.