Item
|
E5CD
|
E5CD-B
|
E5ED
|
E5ED-B
|
Power supply voltage
|
A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
|
Operating voltage range
|
85% to 110% of rated supply voltage
|
Power consumption
|
- Models with option selection of 000:
5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or 1.6 W max. at 24 VDC
- All other models:
6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
|
- Models with option selection of 000:
6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
- All other models:
8.3 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC
|
Sensor input
|
- Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
- Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
|
Input impedance
|
Current input: 150 Ω max., Voltage input: 1 MΩ min.
(Use a 1:1 connection when connecting the ES2-HB/THB.)
|
Control method
|
ON/OFF control or 2-PID control (with auto-tuning)
|
Indication accuracy
|
- Thermocouple: (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max.
- Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
- Analog input: ±0.2% FS ±1 digit max.
- CT input: ±5% FS ±1 digit max.
|
Control
output
|
Relay output
|
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value)
|
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value)
|
Voltage output
(for driving SSR)
|
Output voltage: 12 VDC ± 20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
|
Output voltage: 12 VDC ± 20% (PNP), max. load current: 40 mA, with short-circuit protection circuit
(The maximum load current is 21 mA for models with two control outputs.)
|
Linear current output
|
4 to 20 or 0 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000
|
Auxiliary output
|
Number of outputs
|
2
|
4
|
Output specifications
|
- SPST-NO relay outputs:
250 VAC, 3 A (resistive load)
- Electrical life: 100,000 operations, Minimum applicable load:
10 mA at 5 V (reference values)
|
- SPST-NO relay outputs:
250 VAC, 2 A (resistive load)
- Electrical life: 100,000 operations, Minimum applicable load:
10 mA at 5 V (reference values)
|
- SPST-NO relay outputs, 250 VAC, 2 A (resistive load)
- Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference values)
|
Event
input
|
Number of inputs
|
2
|
2 or 4 (depends on model)
|
External contact input
specifications
|
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
|
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
|
Current flow: Approx. 7 mA per contact
|
Transfer Output
|
Number of outputs
|
1 (depends on model): Transfer output type
|
Output specifications
|
Current output: 4 to 20 mA DC, Load: 500 Ω, Resolution: Approx. 10,000
Linear voltage output: 1 to 5 V DC, Load: 1 kΩ min., Resolution: Approx. 10,000
|
Setting method
|
Digital setting using front panel keys
|
Indication method
|
11-segment digital display, individual indicators, and bar display
Character height: PV: 14.9 mm, SV: 7.1 mm
|
11-segment digital display, individual indicators, and bar display
Character height: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm
Three displays Contents: PV/SV/MV, PV/SV/Multi-SP, PV/SV/Remaining soak time, etc.
Numbers of digits: 4 digits each for PV, SV, and MV displays
|
Multi SP
|
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or serial communications.
|
Bank switching
|
None
|
Other functions
|
Adaptive control, automatic filter adjustment, water-cooling output adjustment, indication data (power ON time monitor, ambient temperature monitor, and control output ON/OFF count monitors), parameter masking, operation after power ON, manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, simple programming, moving average of input value, and display brightness setting
|
Ambient operating temperature
|
−10 to 55°C (with no condensation or icing),
For 3-year warranty: −10 to 50°C with standard mounting (with no condensation or icing)
|
Ambient operating humidity
|
25% to 85%
|
Storage temperature
|
−25 to 65°C (with no condensation or icing)
|
Altitude
|
2,000 m max.
|
Recommended fuse
|
T2A, 250 VAC, time-lag, low-breaking capacity
|
Installation environment
|
Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1)
|
Degree of protection
|
Front panel: IP66, Rear case: IP20, Terminals: IP00
|
Input sampling period
|
50 ms
|
Size in mm (H×W×D)
|
48×48×62
|
48×48×67.4
|
48×96×62
|
48×96×67.4
|