E5C2

Satışla iletişime geçin

(0216) 540 59 91

Fiyat Teklifi İsteyin

Description

E5C2

Easy-to-use, basic temperature controller with analogue dial setting

E5C2; Omron’s basic ON/OFF or PD controller features an analogue setting dial. This compact, low-cost controller has a setting accuracy of 2% of full scale. It incorporates a plug-in socket allowing for DIN-rail or flush mounting.

  • Compact, cost-effective controller
  • Control mode: ON/OFF or P
  • Control output: relay
  • Power supply: 100-120 / 200-240VAC
  • Thermocouple K: 0 to 1200°C, L: 0 to 400°C, Pt100: -50 to 200°C

Expertise

Applications

ON/OFF control

Hot water supply provided by a boiler can be simply controlled with an E5C2. The water temperature is set by the big and easy to operate dial on the front of the controller.

Specifications & ordering info

Standard models (Power supply: 100 to 240 VAC)

Input

Control method

On/OFF

Proportional (P)

Output/Indication method

Relay/No indication

Input/ standard scale (°C)

Thermocouple

K (CA) Chromel vs. Alumel

0 to 200 °C

E5C2-R20K AC100-240 0-200

E5C2-R40K AC100-240 0-200

0 to 300 °C

E5C2-R40K AC100-240 0-300

0 to 400 °C

E5C2-R20K AC100-240 0-400

E5C2-R40K AC100-240 0-400

0 to 600 °C

E5C2-R20K AC100-240 0-600

E5C2-R40K AC100-240 0-600

0 to 800 °C

E5C2-R20K AC100-240 0-800

E5C2-R40K AC100-240 0-800

0 to 1000 °C

E5C2-R20K AC100-240 0-1000

0 to 1200 °C

E5C2-R20K AC100-240 0-1200

J (IC) Iron versus Constantan

0 to 200 °C

E5C2-R20J AC100-240 0-200

0 to 300 °C

E5C2-R20J AC100-240 0-300

0 to 400 °C

E5C2-R20J AC100-240 0-400

Resistance thermometer

Platinum resistance thermometer

-50 to 50 °C

E5C2-R20P-D AC100-240 -50-50

0 to 50 °C

E5C2-R20P-D AC100-240 0-50

0 to 100 °C

E5C2-R20P-D AC100-240 0-100

0 to 200 °C

E5C2-R20P-D AC100-240 0-200

0 to 300 °C

E5C2-R20P-D AC100-240 0-300

0 to 400 °C

E5C2-R20P-D AC100-240 0-400

Thermistor

THE (replaceable element)

0 to 100 °C

E5C2-R20G AC100-240 0-100

100 to 200 °C

E5C2-R20G AC100-240 100-200

150 to 300 °C

E5C2-R20G AC100-240 150-300

Input ranges

Thermocouple

Platinum resistance thermometer

Thermistor

K (CA) chromel vs. alumel

J (IC) iron vs. constantan

Pt100

THE

°C

0 to 200 (5),
0 to 400 (10),
0 to 600 (20),
0 to 800 (20),
0 to 1,000 (25),
0 to 1,200 (25)

0 to 200 (5),
0 to 300 (10),
0 to 400 (10)

-50 to 50 (2),
0 to 50 (1),
0 to 100 (2),
0 to 200 (5),
0 to 300 (10),
0 to 400 (10)

0 to 100 (2) (6 kΩ at 0°C),
100 to 200 (2) (550 Ω ☐ 200°C)

150 to 300 (2) (4 kΩ ☐ 200°C)

Accessories

Functions

Order code

Front connecting socket with finger protection

P2CF-08-E

Back connecting socket (for flush mounting)

P3G-08

Finger protection cover (for P3G-08)

Y92A-48G

Protective front cover (IP66)

Y92A-48B

Specifications

Supply voltage

100 to 240 VAC, 50/60 Hz

Thermocouple input type

K, J (with sensor break detection)

RTD input type

Pt100, THE

Control mode

ON/OFF or P control

Setting method

analog setting

Output

Relay, SPDT, 3 A at 250 VAC

Life expectancy

Electrical: 100,000 operations min.

Setting accuracy

±2% FS max.

Hysteresis

Approx. 0.5% FS (fixed)

Proportional band

3% FS (fixed)

Reset range

5 ±1% FS min.

Control period

20 s

IP Rating front panel

IP40 (IP66 cover available)

IP rating terminals

IP00

Ambient temperature

-10 to 55°C

Size in mm (HxWxD)

48×48×96

Downloads

Datasheet