Description
KM50 Series
Highly visible on-panel energy monitoring
KM50 can measure produced and consumed Power, Current and Voltage as well as leading reactive power, lagging reactive power, power factor, frequency amongst others.
- Assist energy saving analysis with built in energy classification functionality.
- High precision measurements even for currents below 5% of the nominal value through automatic range switchting.
- Able to mesure and distinguished consumed and generated power.
- Measurement of reactive power and power factor.
- Pulse measurement integrated and direct conversion to measure Energy Management KPI (f.i. n. of pcs / kWh).
- No VT required, direct voltage detection / openable CTs
- Multi-colored display
- Modbus communications
- Built-in data logging
Specifications & ordering info
KM50-E Smart power monitor
Applicable circuits
|
Power supply voltage (shared)
|
Dimensions
|
Communications
|
Protocol
|
Order code
|
Single-phase, two wire: 100 to 480 VAC
Single-phase, three wire: 100/200 VAC
Three-phase, three wire: 100 to 480 VAC
Three-phase, four wire: 85 to 277 VAC
|
100 to 240 VAC
|
96 × 48 × 93 (H × W × D)
|
RS-485
|
CompoWay/F: 31 nodes,
Modbus: 99 nodes
(Both are supported by the same model.)
|
KM50-E1-FLK
|
CTs
Rated primary current
|
Rated secondary current
|
Installation
|
Order code
|
5 A
|
Special output
|
Installed separately
|
KM20-CTF-5A
|
50 A
|
KM20-CTF-50A
|
100 A
|
KM20-CTF-100A
|
200 A
|
KM20-CTF-200A
|
400 A
|
KM20-CTF-400A
|
600 A
|
KM20-CTF-600A
|
Note: CT cables are not included with the CTs.
CT Cable
Cable length
|
Order code
|
3 m
|
KM20-CTF-CB3
|
Note: Either use the CT Cable specified by OMRON or use 1.25-B3A crimp terminals and AWG22 wire from J.S.T. Mfg. Co., Ltd.
Specifications
Ratings
Item
|
KM50-E
|
Applicable circuit
|
Single-phase two wire, single-phase three wire, three-phase three wire and three-phase four wire power
|
Rated power supply voltage
|
100 to 240 VAC, 50/60 Hz
|
Allowable supply voltage range
|
85% to 110% of rated power supply voltage
|
Allowable frequency range
|
45 to 65 Hz
|
Power consumption
|
7 VA max.
|
Rated input
|
Rated input voltage
|
100 to 480 VAC (single-phase, 2-wire): Line voltage
100/200 VAC (single-phase, 3-wire): Phase voltage/line voltage
100 to 480 VAC (3-phase, 3-wire): Line voltage
58 to 277 VAC (3-phase, 4-wire): Phase voltage
|
Rated input current
|
5 A, 50 A, 100 A, 200 A, 400 A, or 600 A (primary current of Special CT)
|
Rated frequency
|
50/60 Hz
|
Rated input power
|
With 5-A CT: 4 kW
With 100-A CT: 80 kW
With 400-A CT: 320 kW
|
With 50-A CT: 40 kW
With 200-A CT: 160 kW
With 600-A CT: 480 kW
|
Allowable input voltage
|
110% of rated input voltage (continuous)
|
Allowable input current
|
120% of rated input current (continuous)
|
Ambient operating temperature
|
− 10 to 55°C (with no condensation or icing)
|
Storage temperature
|
− 25 to 65°C (with no condensation or icing)
|
Ambient and storage operation humidity
|
25% to 85%
|
Installation environment
|
Overvoltage category and measurement category: 2, Pollution level: 2
|
Performance
Smart power monitor
Item
|
KM50-E
|
Accuracy
|
Voltage
|
± 1.0% FS ± 1 digit (at ambient temperature of 23°C, rated input, and rated frequency).
However, the accuracy is ± 2.0% FS ± 1 digit for the Vtr line voltage for three-phase, three wire power and the Vrs line voltage for single-phase, three wire power under the same conditions.
|
Current
|
± 1.0% FS ± 1 digit (at ambient temperature of 23°C, rated input, and rated frequency).
However, the accuracy is ± 2.0% FS ± 1 digit for the phase-S current for three-phase, three wire power and the phase-N current for single-phase, three wire power under the same conditions.
|
Active power
Reactive power
|
± 2.0% FS ± 1 digit (at ambient temperature of 23°C, rated input, rated frequency, and a power factor of 1)
Reactive power formula: Reactive power = v × i × sin θ
“v” is the instantaneous voltage and “i” is the instantaneous current.
θ is the phase difference between the voltage and current.
|
Frequency
|
± 0.3 Hz ± 1 digit (at ambient temperature of 23°C, rated input, and rated frequency)
|
Power factor
|
± 5.0% FS ± 1 digit (at ambient temperature of 23°C, rated input, rated frequency, and power factor = 0.5 to 1 to 0.5)
Power factor formula: Power factor = Active power/Apparent power
|
Temperature
|
± 5°C two hours after the power is turned ON (after setting the offset to match the ambient environment)
|
Communications
|
Communications method
|
RS-485 (two wire half-duplex)
|
Sync method
|
Start-stop
|
Unit number setting
|
CompoWay/F: 0 to 99, Modbus: 1 to 99
|
Baud rate
|
1.2, 2.4, 4.8, 9.6, 19.2, 38.4 kbps
|
Transmission code
|
CompoWay/F: ASCII, Modbus: Binary
|
Data length
|
7, 8 bits
|
Stop bit length
|
1, 2 bits
|
Vertical parity
|
Even, odd, or none
|
Maximum transmission distance
|
500 m
|
Maximum number of connected Power Monitors
|
CompoWay/F: 31, Modbus: 99
|
CTs
Item
|
KM20-CTF-5A
|
KM20-CTF-50A
|
KM20-CTF-100A
|
KM20-CTF-200A
|
KM20-CTF-400A
|
KM20-CTF-600A
|
Rated primary current
|
5 A
|
50 A
|
100 A
|
200 A
|
400 A
|
600 A
|
Secondary winding
|
3,000 turns
|
6,000 turns
|
9,000 turns
|
Application frequency
|
10 Hz to 5 kHz
|
Insulation resistance
|
Between output terminal and external case: 50 M Ω min. (at 500 VDC)
|
Dielectric strength
|
Between output terminal and external case: 2,000 VAC for 1 min
|
Protective element
|
7.5 V clamp element
|
Allowable number of connections/disconnections
|
100 times
|
Inner diameter
|
10 dia.
|
16 dia.
|
24 dia.
|
37 dia.
|
Operating temperature and humidity range
|
− 20 to 60°C 85% (with no condensation)
|
Storage temperature and humidity range
|
− 30 to 65°C 85% (with no condensation)
|