G7S Relays with forcibly guided contacts

The slim G7S-_-E relay family with forcibly guided contacts is available as a six-pole type in two different contact combinations. Terminals are arranged for easy PCB layout. It can be soldered directly to a PCB or used together with the P7SA sockets.

  • Forcibly guided contacts
  • Conforms to EN 50205
  • NO contacts: 10 A at 250 VAC and 10 A at 30 VDC, NC contacts: 6 A at 250 VAC and 6 A at 30 VDC (for resistive loads)
  • Reinforced insulation between inputs and outputs and poles
  • 4- and 6-pole relays available

 

Datasheet
Click for other programmable safety system

Specifications & ordering info

Relays with forcibly guided contacts

Type

Sealing

Poles

Contacts

Rated voltage

Order code

Standard

Flux-tight

6 poles

4PST-NO, DPST-NC

24 VDC

G7S-4A2B-E

3PST-NO, 3PST-NC

G7S-3A3B-E

Sockets

Type

LED indicator

Rated voltage

Order code

Track-mounting

Track mounting and screw mounting
possible

Yes

24 VDC

P7S-14F-END

Back-mounting

PCB terminals

No

P7S-14P-E

Specifications

Ratings

Coil

Rated voltage

Rated current (mA)

Coil resistance (Ω)

Max. voltage (V)

Power consumption (W)

24 VDC

30

800

110%

Approx. 0.8

Contacts

Item

Resistive load

Rated load

NO contact

10 A at 250 VAC, 10 A at 30 VDC

NC contact

6 A at 250 VAC, 6 A at 30 VDC

Rated carry current

NO contact

10 A

NC contact

6 A

Item

Resistive load

Maximum switching voltage

250 VAC, 30 VDC

Maximum switching current

NO contact

10 A

NC contact

6 A

G7S-_-E Characteristics of Sockets

Model

P7S-14F-END

P7S-14P-E

Continuous current

10 A

Dielectric strength

2000 VAC for 1 min. between terminals

Insulation resistance

1000 MΩ min.

Ambient operating humidity

25 to 85%

5 to 85%

Characteristics

Contact resistance

100 mΩ max.

Operating time

50 ms max.

Release time

50 ms max.

Maximum operating frequency

Mechanical

18,000 operations/h

Rated load

1,800 operations/h

Insulation resistance

100 MΩ min.

Durability

Mechanical

10,000,000 operations min. (at approx. 18,000 operations/h)

Electrical

100,000 operations min. (at the rated load and approx. 1,800 operations/h)

Inductive load switching capability

(IEC60947-5-1)

NO Contact

AC15 AC240V 5A, DC13 DC24V 2A

NC Contact

AC15 AC240V 3A, DC13 DC24V 2A

Ambient operating temperature

-25 to 70°C (with no icing or condensation)

Ambient operating humidity

5% to 85%

Note: The values listed above are initial values.

Please check Omron in the Internet for updated information on product reliability data and the SISTEMA libraries: http://industrial.omron.eu/safety