Points
|
Type
|
Ranges
|
Resolution
|
Accuracy
|
Conversion
time
|
Remarks
|
Connection type
|
Order code
|
4
|
Analog input
|
0 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V,
4 to 20 mA
|
1/8,000
|
V: 0.2% of PV
I: 0.4% of PV
|
250 µs/point
|
Offset/gain adjustment, peak hold,
moving average, alarms
|
M3
|
CS1W-AD041-V1
|
8
|
Analog input
|
M3
|
CS1W-AD081-V1
|
16
|
Analog input
|
0.2% of PV
|
2 × MIL (34p.)
|
CS1W-AD161
|
4
|
Analog output
|
0 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V,
4 to 20 mA
|
1/4,000
|
V: 0.3% of PV
I: 0.5% of PV
|
1 ms/point
|
Offset/gain adjustment
|
M3
|
CS1W-DA041
|
8
|
Voltage output
|
0 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V
|
0.3% of PV
|
Offset/gain adjustment, output hold
|
M3
|
CS1W-DA08V
|
8
|
Current output
|
4 to 20 mA
|
0.5% of PV
|
M3
|
CS1W-DA08C
|
4 + 4
|
Analog in + output
|
0 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V
(4 to 20 mA input)
|
1/8,000
|
V in: 0.2% of PV
I in: 0.4% of PV
out: 0.3% of PV
|
1 ms/point
|
Offset/gain adjustment, scaling, peak hold, moving average, alarms, output hold
|
M3
|
CS1W-MAD44
|
4
|
Process input
|
4 to 20 mA,
0 to 20 mA,
0 to 10 V,
-10 to 10 V,
0 to 5 V,
-5 to 5 V,
1 to 5 V,
1 to 1.25 V,
-1.25 to 1.25 V
|
1/64,000
|
0.05% of PV
|
5 ms/point
|
Configurable alarms, maintenance
functions, user-defined scaling, zero/span adjustment, square root, totaliser.
|
M3
|
CS1W-PDC11
|
8
|
Process input
|
-10 to 10 V,
0 to 5 V,
1 to 5 V,
4 to 20 mA
|
1/16,000
|
0.3% of PV
|
62.5 ms/point
|
Configurable alarms, zero/span adjustment, square root
|
M3
|
CS1W-PDC55
|
4
|
Thermocouple input
|
B, E, J, K, L, N, R, S, T,
U, WRe5-26, PLII,
-100 to 100 mV
|
1/64,000
|
0.05% of PV
|
5 ms/point
|
Configurable alarms (absolute +
rate-of-change), peak hold,
maintenance functions
|
M3
|
CS1W-PTS11
|
4
|
Resistance thermometer input
|
Pt50, Pt100 JPt100, Ni508.4
|
1/64,000
|
0.05% of PV
|
5 ms/point
|
Configurable alarms (absolute +
rate-of-change), peak hold,
maintenance functions
|
M3
|
CS1W-PTS12
|
4
|
Thermocouple input
|
B, J, K, L, R, S, T
|
0.1°C
|
0.3% of PV
|
62.5 ms/point
|
4 configurable alarm outputs
|
M3
|
CS1W-PTS51
|
4
|
Resistance thermometer input
|
Pt100, JPt100
|
0.1°C
|
0.3% of PV
|
62.5 ms/point
|
4 configurable alarm outputs
|
M3
|
CS1W-PTS52
|
8
|
Thermocouple input
|
B, J, K, L, R,S, T
|
0.1°C
|
0.3% of PV
|
31.2 ms/point
|
Configurable alarms per channel
|
M3
|
CS1W-PTS55
|
8
|
Resistance thermometer input
|
Pt100, JPt100
|
0.1°C
|
0.3% of PV
|
31.2 ms/point
|
Configurable alarms per channel
|
M3
|
CS1W-PTS56
|
4
|
2-Wire transmitter input
|
1 to 5 V,
4 to 20 mA
|
1/4,096
|
0.2% of FS
|
25 ms/point
|
Built-in power supply for transmitter, configurable alarms, square root,
rate-of-change, etc.
|
M3
|
CS1W-PTW01
|
8
|
Power transducer input
|
-1 to 1 mA,
0 to 1 mA
|
1/4,096
|
0.2% of FS
|
25 ms/point
|
Inrush current limiter, configurable alarms, averaging, etc.
|
M3
|
CS1W-PTR01
|
8
|
Power transducer input
|
-100 to 100 mV,
0 to 100 mV
|
1/4,096
|
0.2% of FS
|
25 ms/point
|
Inrush current limiter, configurable alarms, averaging, etc.
|
M3
|
CS1W-PTR02
|
4
|
Pulse rate input
|
20000 pps, voltage,
open collector, contact
|
up to
1/32,000
|
–
|
25 ms/point
|
Averaging, totaliser
|
M3
|
CS1W-PPS01
|
4
|
Isolated control output
|
1 to 5 V,
4 to 20 mA
|
1/4,000
|
I: 0.1% of FS
V: 0.2% of FS
|
25 ms/point
|
Output readback, high/low/rate limiting, disconnection alarm, zero/span
adjustment
|
M3
|
CS1W-PMV01
|
4
|
Isolated control output
|
-10 to 10 V,
0 to 10 V,
-5 to 5 V,
0 to 5 V,
-1 to 1 V,
0 to 1 V
|
1/4,000
|
0.1% of FS
|
10 ms/point
|
High/low/rate limiting, output hold,
zero/span adjustment
|
M3
|
CS1W-PMV02
|