Number of safety input points |
12 |
Number of safety output points |
4 |
– |
Number of test output points |
12 |
OMRON special safety input device
|
Connection unavailable |
LED indication |
[V0] LED, [IN⬜] LED x 12, [V1] LED,
[OUT⬜] LED x 4, [MS] LED, [NS] LED,
[PORT⬜LINK] LED x 2 |
[V0] LED, [IN⬜] LED x 12,
[V1] LED, [MS] LED, [NS] LED,
[PORT⬜LINK] LED x 2 |
Hardware switch setting |
[IP ADDRESS] switch x3 (MODE, x16, x1)
Factory default
GI-SMD1624: 192.168.250.2 [IP ADDRESS] Switch= “002”
GI-SID1224: 192.168.250.3 [IP ADDRESS] Switch= “003“
|
Safety input type |
IEC61131-2 type3 PNP (sinking inputs) |
Safety input current |
6 mA max. |
Safety input ON voltage |
11 VDC min. |
Safety input OFF voltage/OFF current |
5 VDC max./1 mA max. |
Safety output type |
Source output (for PNP) |
Safety output rated current |
0.5 A max. |
|
Maximum total safety output current |
2.0 A |
Safety output ON residual voltage |
1.2 V max.
(between V1 and each output terminal) |
Safety output OFF residual voltage |
2.0 V max.
(between G1 and each output terminal) |
Safety output leakage current |
0.1 mA max. |
Test output type |
Source output (for PNP) |
Test output rated current |
0.7 A max. |
Maximum total test output current |
5.0 A |
Test output ON residual voltage |
1.2 V max. (between V0 and each output terminal) |
Test output leakage current |
0.1 mA max. |
External dimensions
|
170 (W) x 65 (H) x 55 (D) |
Weight |
400 g |
Number of communications that can be set
between NX Units |
254 ports max.
|
Unit power
supplies |
Power supply voltage |
24 VDC (20.4 to 28.8 VDC) |
Current consumption
|
250 A max. |
Inrush current |
On cold start at normal temperature50 A max., 0.1 ms max. |
Power supply terminal
current carrying capacity
|
5 A |
Insulation type |
No insulation: Between unit power supply terminal and internal circuit |
Output power
supply |
Power supply voltage |
24 VDC (20.4 to 28.8 VDC) |
|
Current consumption |
50 A max. |
Inrush current |
On cold start at normal temperature
50 A max., 0.1 ms max. |
Power supply terminal
current carrying capacity
|
5 A |
Insulation type |
Photocoupler insulation |
External
connection
terminal |
Communication connector |
EtherNet/IP communication RJ45 x 2 |
Screwless clamp terminal
block |
Top terminal block
- Functional earthing
- Unit power supply
- Input/Test output
Bottom terminal block
- Output power supply
- Output/Input/Test output
|
Top terminal block
- Functional earthing
- Unit power supply
- Input/Test output
Bottom terminal block
|
Inter-terminal
connection
diagram |
V0/G0 Unit power supply |
 |
V1/G1 Output power supply |
 |
|
Installation direction and restriction |
No restriction |
Protective function |