Ambient operating temperature
|
-20 to 60°C (with no condensation or icing)
|
Storage temperature
|
-25 to 65°C (with no condensation or icing)
|
Operating voltage range
|
85% to 110% of rated operating voltage
|
Rated power supply frequency
|
50/60 Hz±5 Hz (AC power supply)
|
Output relays
(1 × SPDT, normally closed operation)
|
Resistive load
|
5 A at 250 VAC or at 30 VDC
|
Maximum contact voltage
|
250 VAC or 30 VDC
|
Maximum contact current
|
5 A
|
Maximum switching capacity
|
1,250 VA, 150 W
|
Mechanical life
|
10,000,000 operations
|
Electrical life
|
50,000 operations at 5 A, 250 VAC or 30 VDC
|
Degree of protection
|
Terminal section: IP20
|
Case material
|
PC and ABS
|
Weight
|
Approx. 150 g
|
Operating power
|
Isolated power supply
|
2.0 VA/1.1 W max. at 24 VAC/DC, 4.6 VA max. at 100 to 240 VAC
|
Operate (SV)
|
Operating value setting range
|
10% to 100% of maximum measuring current
|
Operating value
|
100% operation at set value
|
Reset (HYS.)
|
Hysteresis
|
5% of operating value (fixed)
|
Resetting method
|
Manual reset/automatic reset (switchable)
Manual reset: Turn OFF operating power for 1 s or longer
|
Operating time (T)
|
0.1 to 30 s
|
Operating power ON lock (LOCK)
|
0 to 30 s (The startup lock timer starts when the input has reached approximately 30% or more of the set value.)
Note: Enabled only for overcurrent operation
|
Repeat error
|
Operating value
|
±0.5% full scale (at 25°C and 65% humidity, rated power supply voltage, DC or 50/60 Hz sine wave input)
|
Operating time
|
±50 ms (at 25°C and 65% humidity, rated power supply voltage)
|
Input frequency range
|
K8AK-AW1/-AW2
|
DC input or AC input (45 to 65 Hz)
|
K8AK-AW3
|
AC input (45 to 65 Hz)
|
Overload capacity
|
K8AK-AW1/-AW2
|
Continuous input at 120% of maximum input, 1 s at 150%
|
K8AK-AW3
|
Continuous input at 120%, 30 s at 200%, and 1 s at 600% with an OMRON CT (K8AC-CT200L)
|
Indicators
|
Power (PWR): Green LED, relay output (RY): Yellow LED, alarm outputs (ALM): Red LED
|
Applicable standards
|
Conforming standards
|
EN 60947-5-1
Installation environment (pollution level 2, installation category III)
|
EMC
|
EN 60947-5-1
|
Safety standards
|
UL 508 (Recognition), Korean Radio Waves Act (Act 10564), CSA and CCC
|
Size in mm (H × W × D)
|
90 × 22.5 × 100
|