Description
G7Z
Compact 160 Amp Power Relay
G7Z series provides a compact, cost efficient solution for applications such as inverters, UPS, solar and fuel-cell battery circuits. Relay in combination with auxiliary contact block meets EN 60947-4-1. Coil ratings are available in 12 and 24 VDC. Power consumption is less than 4 watts.
- Switching current 160 A (40 A rating / 4-pole / IEC-AC1)
- Switching voltage 440 VAC
- Safety function with mirror contacts in various configurations
- Power consumption less than 4 Watts
- Low Switching Noise (70 dB)
Specifications & ordering info
Ordering information
Relay with Auxiliary Contact Block (for Screw Terminals)
Contact configuration
|
Rated voltage
|
Order code
|
Relay
|
Auxiliary contact block
|
4PST-NO
|
DPST-NO
|
12, 24 VDC
|
G7Z-4A-20Z
|
SPST-NO/SPST-NC
|
G7Z-4A-11Z
|
DPST-NC
|
G7Z-4A-02Z
|
3PST-NO/SPST-NC
|
DPST-NO
|
G7Z-3A1B-20Z
|
SPST-NO/SPST-NC
|
G7Z-3A1B-11Z
|
DPST-NC
|
G7Z-3A1B-02Z
|
DPST-NO/DPST-NC
|
DPST-NO
|
G7Z-2A2B-20Z
|
SPST-NO/SPST-NC
|
G7Z-2A2B-11Z
|
DPST-NC
|
G7Z-2A2B-02Z
|
Specifications
Coil ratings
Rated voltage
|
Rated current
|
Coil resistance
|
Must operate voltage
|
Must release voltage
|
Max. voltage
|
Power consumption (approx.)
|
% of rated voltage
|
12 VDC
|
333 mA
|
39 Ω
|
75% max.
|
10% min.
|
110%
|
Approx. 3.7 W
|
24 VDC
|
154 mA
|
156 Ω
|
Note • Rated current and coil resistance were measured at a coil temperature of 23°C with coil resistance of ±15%.
- Operating characteristics were measured at a coil temperature of 23°C.
- The maximum allowable voltage is the maximum value of the fluctuation range for the Relay coil operating power supply and was measured at an ambient temperature of 23°C.
Contact Ratings – Relay
Item
|
G7Z-4A-_Z, G7Z-3A1B-_Z, G7Z-2A2B-_Z
|
Resistive load
|
Inductive load cos phi = 0.3
|
Resistive load L/R = 1 ms
|
Contact structure
|
Double break
|
Contact material
|
Ag alloy
|
Rated load
|
NO
|
40 A at 440 VAC
|
22 A at 440 VAC
|
5 A at 110 VDC
|
NC
|
25 A at 440 VAC
|
10 A at 440 VAC
|
5 A at 110 VDC
|
Rated carry current
|
NO
|
40 A
|
22 A
|
5 A
|
NC
|
25 A
|
10 A
|
5 A
|
Maximum contact voltage
|
480 VAC
|
125 VDC
|
Maximum contact current
|
NO
|
40 A
|
NC
|
25 A
|
Maximum switching capacity
|
NO
|
17,600 VA
|
9,680 VA
|
550 W
|
NC
|
11,000 VA
|
4,400 VA
|
550 W
|
Failure rate P value (reference value)
|
2 A at 24 VDC
|
Note: The ratings for the auxiliary contact block mounted on the G7Z are the same as those for the G73Z auxiliary contact block.
Contact Ratings – Auxiliary Contact Block
Item
|
G7Z-4A-_Z, G7Z-3A1B-_Z, G7Z-2A2B-_Z
|
Resistive load
|
Inductive load cos phi = 0.3
|
Resistive load L/R = 1 ms
|
Contact structure
|
Double break
|
Contact material
|
Au clad + Ag
|
Rated load
|
1 A at 440 VAC
|
0.5 A at 440 VAC
|
5 A at 110 VDC
|
Rated carry current
|
1 A
|
Maximum contact voltage
|
480 VAC
|
125 VDC
|
Maximum contact current
|
1 A
|
Maximum switching capacity
|
440 VA
|
220 VA
|
110 W
|
Failure rate P value (reference value)
|
1 mA at 5 VDC
|